Daikin RXYQ22M7W1B [178/182] Sound level

Daikin RXYQ16M7W1B [178/182] Sound level
18
10
Systems Outdoor Units
177
Inverter heat pump RXYQ5M7W1B, RXYQ8,10M8W1B
10 Sound level
10-1 Sound level data
NOTES
Data is valid at free field condition (measured in a semi-anechoic rrom)
dBA = A-weighted sound pressure level. (A-scale according to IEC)
Reference acoustic pressure 0dB = 20µPa
If sound is measured under actual installation conditions, it is normally over the set value, due to environmental noise and sound reflection.
10-2 Sound pressure spectrum
Model
Sound pressure level
Sound power level
H Measuring location
RXYQ5M 56 72
RXYQ8M 57 78
RXYQ10M 58 78
RXYQ12M 60 80
RXYQ14M 60 80
RXYQ16M 60 80
RXYQ18M 61 81
RXYQ20M 61 81
RXYQ22M 62 82
RXYQ24M 62 82
RXYQ26M 62 82
RXYQ28M 63 83
RXYQ30M 63 83
RXYQ32M 63 83
RXYQ34M 64 84
RXYQ36M 64 84
RXYQ38M 64 84
RXYQ40M 64 84
RXYQ42M 64 84
RXYQ44M 65 85
RXYQ46M 65 85
RXYQ48M 65 85
RXYQ5M7W1B 3TW25797-1 RXYQ8M8W1B 3TW25807-1 RXYQ10M8W1B 3TW25817-1
RXYQ12,14M8W1B 3TW25827-1 RXYQ16M8W1B 3TW25847-1
Microphone
Coil
Switchbox
60Hz
50Hz
Octave band center frequency (Hz)
Sound pressure level (dB)
Octave band center frequency (Hz)
Sound pressure level (dB)
Octave band center frequency (Hz)
Sound pressure level (dB)
Octave band center frequency (Hz)
Sound pressure level (dB)
Octave band center frequency (Hz)
Sound pressure level (dB)

Содержание