Daikin RXYQ22M7W1B [8/182] 2 technical specifications

Daikin RXYQ16M7W1B [8/182] Specifications
18
1
Systems Outdoor Units
7
Inverter heat pump RXYQ5M7W1B, RXYQ8,10M8W1B
1 Specifications
1-2 Technical Specifications
1-2-3 8,10HP
RXYQ8M8W1B RXYQ10M8W1B
OPERATION RANGE Cooling Minimum °CDB -5.0 -5.0
Maximum °CDB 43.0 43.0
Heating Minimum °CWB -20.0 -20.0
Maximum °CWB 15.5 15.5
SOUND LEVEL (NOMINAL) Cooling Sound Power dBA 78.0 78.0
Sound Pressure dBA 57.0 58.0
Heating Sound Pressure dBA 57.0 58.0
REFRIGERANT Type R-410A R-410A
Charge kg 8.6 9.6
Control Expansion valve (electronic type) Expansion valve (electronic type)
N° of circuits 1 1
REFRIGERANT OIL Type Synthetic (ether) oil Synthetic (ether) oil
Charged Volume l 1.9+1.6 1.9+1.6
PIPING CONNECTIONS Liquid Type Flare connection Flare connection
Diameter (OD) mm 9.52 9.52
Gas Type Braze connection Braze connection
Diameter (OD) mm 19.1 22.2
Heat Insulation Both liquid and gas pipes Both liquid and gas pipes
Max. total length m 300 300
DEFROST METHOD Reversed cycle Reversed cycle
DEFROST CONTROL Sensor for outdoor heat exchanger temperature Sensor for outdoor heat exchanger temperature
CAPACITY CONTROL METHOD Inverter controlled Inverter controlled
CAPACITY CONTROL [%] 14 to 100 14 to 100
SAFETY DEVICES HPS HPS
Fan motor overcurrent protector Fan motor overcurrent protector
Inverter overload protector Inverter overload protector
Over current relay Over current relay
PC board fuse PC board fuse
STANDARD ACCESSORIES Item Installation and operation manual Installation and operation manual
Quantity 1 1
Item Connection pipes Connection pipes
Quantity 3 3
Item Clamps Clamps
Quantity 1 1
3TW25801-1A
NOTES
1 Nominal cooling capacities are based on:
Indoor temperature: 27°CDB, 19°CWB
Outdoor temperature: 35°CDB
Equivalent refrigerant piping length: 7.5m
Level difference: 0m
2 Nominal heating capacities are based on:
Indoor temperature: 20°CDB
Outdoor temperature: 7°CDB, 6°CWB
Equivalent refrigerant piping length: 7.5m
Level difference: 0m
3 Sound power level is an absolute value that a sound source generates.
4 Sound pressure level is a relative value, depending on the distance and
acoustic environment. For more details, please refer to sound level
drawings.
5 Sound values are measured in a semi-anechoic room.