Daikin RXYQ22M7W1B [6/182] 2 technical specifications

Daikin RXYQ22M7W1B [6/182] 2 technical specifications
18
1
Systems Outdoor Units
5
Inverter heat pump RXYQ5M7W1B, RXYQ8,10M8W1B
1 Specifications
1-2 Technical Specifications
1-2-1 5HP
RXYQ5M7W1B
REFRIGERANT Type R-410A
Charge kg 5.6
Control Expansion valve (electronic type)
N° of circuits 1
REFRIGERANT OIL Type Synthetic (ether) oil
Charged Volume l 1.2
PIPING CONNECTIONS Liquid Type Flare connection
Diameter (OD) mm 9.52
Gas Type Flare connection
Diameter (OD) mm 15.9
Heat Insulation Both liquid and gas pipes
Max. total length m 300
DEFROST METHOD Reversed cycle
DEFROST CONTROL Sensor for outdoor heat exchanger temperature
CAPACITY CONTROL METHOD Inverter controlled
CAPACITY CONTROL [%] 24 to 100
SAFETY DEVICES HPS
Fan motor overcurrent protector
Inverter overload protector
PC board fuse
STANDARD ACCESSORIES Item Installation and operation manual
Quantity 1
Item Additional refrigerant label
Quantity 1
3TW25791-1A
NOTES
1 Nominal cooling capacities are based on:
Indoor temperature: 27°CDB, 19°CWB
Outdoor temperature: 35°CDB
Equivalent refrigerant piping length: 7.5m
Level difference: 0m
2 Nominal heating capacities are based on:
Indoor temperature: 20°CDB
Outdoor temperature: 7°CDB, 6°CWB
Equivalent refrigerant piping length: 7.5m
Level difference: 0m
3 Sound power level is an absolute value that a sound source generates.
4 Sound pressure level is a relative value, depending on the distance and
acoustic environment. For more details, please refer to sound level
drawings.
5 Sound values are measured in a semi-anechoic room.