Daikin RXYQ10MY1K [127/310] C monitor mode

Daikin RXYQ8MY1K [127/310] C monitor mode
Field Setting Si39-502A
116 Test Operation
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
Setting item 0 Display contents of Various setting
No. Setting item
LED display
Data display
H1P H2P H3P H4P H5P H6P H7P
0 Various setting
9777777
See below
1 C/H unified address
9777778
Lower 6 digits
2 Low noise/demand address
9777787
3 Not used
9777788
4 Airnet address
9777877
5 Number of connected indoor units
9777878
6 Number of connected BS units
9777887
7
Number of connected zone units
(excluding outdoor and BS unit)
9777888
8 Number of outdoor units
9778777
9 Number of connected BS units
9778778
Lower 4 digits:
upper
10 Number of connected BS units
9778787
Lower 4 digits:
lower
11
Number of zone units (excluding
outdoor and BS unit)
9778788
Lower 6 digits
12 Number of terminal blocks
9778877
Lower 4 digits:
upper
13 Number of terminal blocks
9778878
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
8778887
Malfunction
code table
Refer page
149, 150.
15
Contents of malfunction
(1 cycle before)
8778888
16
Contents of malfunction
(2 cycle before)
8787777
20 Contents of retry (the latest)
8787877
21 Contents of retry (1 cycle before)
8787878
22 Contents of retry (2 cycle before)
8787887
EMG operation /
backup operation
setting
ON
9778777
OFF
9777777
Defrost select setting Short
9777877
Medium
9777977
Long
9777777
Te setting H
9777787
M
9777797
L
9777777
Tc setting H
9777778
M
9777779
L
9777777
c. Monitor mode
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE (BS1) button when in
Setting mode 1.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
Monitor mode.
Push the MODE (BS1) button and
returns to Setting mode 1.
(V2765)