Daikin RXYQ10MY1K [181/310] Outdoor unit std compressor motor overcurrent lock

Daikin RXYQ10MY1K [181/310] Outdoor unit std compressor motor overcurrent lock
Troubleshooting by Indication on the Remote Controller Si39-502A
170 Troubleshooting
3.17
E6
Outdoor Unit:
STD Compressor Motor Overcurrent/
Lock
Remote
Controller
Display
E6
Applicable
Models
RXYQ8~30MY1K (E), YLK (E)
Method of
Malfunction
Detection
Detects the overcurrent with current sensor (CT).
Malfunction
Decision
Conditions
Malfunction is decided when the detected current value exceeds the below mentioned value for
2 seconds.
400 V unit : 15.0 A
Supposed
Causes
Closed stop value
Obstacles at the discharge port
Improper power voltage
Faulty magnetic switch
Faulty compressor
Faulty current sensor