Daikin RXYQ10MY1K [150/310] Troubleshooting by remote controller

Daikin RXYQ8MY1K [150/310] Troubleshooting by remote controller
Si39-502A Troubleshooting by Remote Controller
Troubleshooting 139
2. Troubleshooting by Remote Controller
2.1 The INSPECTION / TEST Button
The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
Normal
mode
Inspection
mode
Test
operation
mode
Local
setting
mode
Service
mode
Depress Inspection/Test Operation button
for more than 4 seconds.
Depress Inspection/Test Operation button
for more than 4 seconds.
Press Inspection/Test Operation button once.
Press Inspection/Test Operation button once.
Or after 30 minutes
After 10 seconds
Press Inspection/Test Operation
button once.
Press Inspection/Test Operation
button once.
Indoor unit settings can be made
Filter sign time
Air flow direction
Others
Following codes can be checked.
Malfunction codes
Indoor model code
Outdoor model code
Service data can be obtained.
Malfunciton code history
Temperature data of various sections
Service settings can be made.
Forced fan ON
Air flow direction/volume setting
Thermostat is forcibly turned on.
(V0815)