Daikin RXYQ10MY1K [209/310] Outdoor unit power supply insufficient or instantaneous failure

Daikin RXYQ10MY1K [209/310] Outdoor unit power supply insufficient or instantaneous failure
Troubleshooting by Indication on the Remote Controller Si39-502A
198 Troubleshooting
3.41
U2
Outdoor Unit: Power Supply Insufficient or
Instantaneous Failure
Remote
Controller
Display
U2
Applicable
Models
RXYQ8~30MY1K (E), YLK (E)
Method of
Malfunction
Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Decision
Conditions
When the capacitor above only has a voltage of 380 V or less.
Supposed
Causes
Power supply insufficient
Instantaneous failure
Open phase
Defect of inverter PC board
Defect of outdoor control PC board
Main circuit wiring defect

Содержание

Скачать