Daikin RXYQ10MY1K [228/310] Improper combination of optional controllers for centralized control

Daikin RXYQ8MY1K [228/310] Improper combination of optional controllers for centralized control
Si39-502A Troubleshooting (OP: Central Remote Controller)
Troubleshooting 217
4.3
MA
Improper Combination of Optional Controllers for
Centralized Control
Remote
Controller
Display
MA
Applicable
Models
Central remote controller
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
When the schedule timer is set to individual use mode, other central component is present.
When multiple master controller are present.
When the remote control adapter is present.
Supposed
Causes
Improper combination of optional controllers for centralized control
More than one master controller is connected
Defect of PC board of optional controller for centralized control