Daikin RXYQ10MY1K [218/310] Indoor unit malfunction of transmission between indoor and outdoor units in the same system

Daikin RXYQ10MY1K [218/310] Indoor unit malfunction of transmission between indoor and outdoor units in the same system
Si39-502A Troubleshooting by Indication on the Remote Controller
Troubleshooting 207
3.47
U9
Indoor Unit: Malfunction of Transmission Between
Indoor and Outdoor Units in the Same System
Remote
Controller
Display
U9
Applicable
Models
All models of indoor units
Method of
Malfunction
Detection
Detect the malfunction signal of any other indoor unit within the system concerned.
Malfunction
Decision
Conditions
When the malfunction decision is made on any other indoor unit within the system concerned.
Supposed
Causes
Malfunction of transmission within or outside of other system
Malfunction of electronic expansion valve in indoor unit of other system
Defect of PC board of indoor unit in other system
Improper connection of transmission wiring between indoor and outdoor unit