Daikin RXYQ10MY1K [199/310] Outdoor unit malfunction of inverter radiating fin temperature rise

Daikin RXYQ8MY1K [199/310] Outdoor unit malfunction of inverter radiating fin temperature rise
Troubleshooting by Indication on the Remote Controller Si39-502A
188 Troubleshooting
3.32
L4
Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise
Remote
Controller
Display
L4
Applicable
Models
RXYQ8~30MY1K (E), YLK (E)
Method of
Malfunction
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Decision
Conditions
When the temperature of the inverter radiation fin increases above 98°C.
Supposed
Causes
Actuation of fin thermal (Actuates above 98°C)
Defect of inverter PC board
Defect of fin thermistor
Troubleshooting
Refer to Thermistor Resistance / Temperature Characteristics table on P277.
(V2811)
Resistance
check of the radiator fin
thermistor
Defect of power unit radiation.
Intake port is clogged
Radiator fin is dirty
Outdoor temperature is high
NO
Replace the thermistor.
YES
Abnormal
Is reset possible?
Reset and operate.
Normal
Replace the inverter PC board
NO
YES
Temperature
of the radiator fin rises.
Actuates at min.
98 ˚C
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.