Troubleshooting by Remote Controller Si39-502A
148 Troubleshooting
Outdoor
Unit
LA 999Malfunction of power unit
LC 999Malfunction of transmission between inverter and
control PC board
192
P1 999Inverter over-ripple protection 194
P4 999Malfunction of inverter radiating fin temperature rise
sensor
195
System
U0 879Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
196
U1 999Reverse phase / open phase 197
U2 999Power supply insufficient or instantaneous failure 198
U3 999Check operation is not conducted. 200
U4 999Malfunction of transmission between indoor and
outdoor units
201
U5 999Malfunction of transmission between remote
controller and indoor unit
203
U5 787Failure of remote controller PC board or setting
during control by remote controller
203
U7 999Malfunction of transmission between outdoor units 204
U8 997Malfunction of transmission between main and sub
remote controllers (malfunction of sub remote controller)
206
U9 999Malfunction of transmission between indoor unit and
outdoor unit in the same system
207
UA 999Improper combination of indoor and outdoor units,
indoor units and remote controller.
209
UC 888Address duplication of central remote controller 210
UE 999Malfunction of transmission between central remote
controller and indoor unit
211
220
UF 999System is not set yet 213
UH 999Malfunction of system, refrigerant system address
undefined
214
Central
Remote
Controller
and
Schedule
Timer
M1 8 or 79 9Central remote controller PC board defect
Schedule timer PC board defect
215
222
M8 8 or 79 9Malfunction of transmission between optional
controllers for centralized control
216
223
MA 8 or 79 9Improper combination of optional controllers for
centralized control
217
224
MC 8 or 79 9Address duplication, improper setting 219
226
Heat
Reclaim
Ventilation
64 879Indoor units air thermistor error
65 879Outside air thermistor error
6A 879Damper system alarm
6A 999Damper system + thermistor error
6F 879Malfunction of simple remote controller
6H 879Malfunction of door switch or connector
94 999Internal transmission error
8: ON 7: OFF 9: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No. Malfunction contents Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.