Daikin RXYQ10MY1K [211/310] Outdoor unit check operation not executed

Daikin RXYQ8MY1K [211/310] Outdoor unit check operation not executed
Troubleshooting by Indication on the Remote Controller Si39-502A
200 Troubleshooting
3.42
U3
Outdoor Unit: Check Operation not executed
Remote
Controller
Display
U3
Applicable
Models
RXYQ8~30MY1K (E), YLK (E)
Method of
Malfunction
Detection
Check operation is executed or not
Malfunction
Decision
Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed
Causes
Check operation is not executed.
Troubleshooting
(V3052)
Has the
check operation
performed on Outdoor
unit PC board?
Press the BS4 on PC board on the
master outdoor unit for 5 seconds
or more to execute check
operation.
Replace the main PC board on the
outdoor unit.
NO
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.