Daikin RXYQ10MY1K [223/310] Troubleshooting

Daikin RXYQ8MY1K [223/310] Troubleshooting
Troubleshooting by Indication on the Remote Controller Si39-502A
212 Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is
the power supply
turned on for indoor units
displaying
malfunction?
Is
transmission wiring
disconnected or
wired incorrectly?
Is
the transmission
wiring with the master
controller disconnected
or wired
incorrectly?
Is the
master controller's
connector for setting
master controller
disconnected?
Set the group No.
correctly.
Replace indoor unit PC
board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector
correctly.
Replace the central remote
controller.
Reset power supply
simultaneously for all optional
controllers for centralized
control.
NO
YES
NO
YES
YES
NO
NO
Turn indoor unit's power
supply.
YES
NO
NO
YES
YES
YES
NO
Has
an indoor unit once
connected been removed
or its address
changed?
Is the group
No. of malfunctioning
indoor units set?
Is
transmission with
all indoor units
malfunctioning?
(V2829)