Daikin RXYQ10MY1K [187/310] Outdoor unit abnormal discharge pipe temperature

Daikin RXYQ8MY1K [187/310] Outdoor unit abnormal discharge pipe temperature
Troubleshooting by Indication on the Remote Controller Si39-502A
176 Troubleshooting
3.20
F3
Outdoor Unit: Abnormal Discharge Pipe
Temperature
Remote
Controller
Display
F3
Applicable
Models
RXYQ8~30MY1K (E), YLK (E)
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
Supposed
Causes
Faulty discharge pipe temperature sensor
Faulty connection of discharge pipe temperature sensor
Faulty outdoor unit PC board
Troubleshooting
Refer to Thermistor Resistance / Temperature Characteristics table on P277.
(V3068)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Discharge pipe
temperature is 115˚C
or higher.
Are
the characteristics
of the discharge pipe
thermistor normal?
(3.5~400K)
Replace outdoor unit PC board
(A1P).
Replace the discharge pipe
thermistor.
NO
NO
Out of gas, compression defect,
etc. Defect of the refrigerant
system.
YES
YES