Daikin RXYQ10MY1K [210/310] Troubleshooting

Daikin RXYQ8MY1K [210/310] Troubleshooting
Si39-502A Troubleshooting by Indication on the Remote Controller
Troubleshooting 199
Troubleshooting
K2: Magnetic relay in PC board (A2P)
(V2821)
Correct power supply.
NO
NO
NO
Turn on again.
Replace the outdoor unit
PC board (A1P).
YES
YES
YES
Is
220 ~ 240 V
at the connector X1A of
inverter PC
board.
Replace the inverter PC
board.
Replace the inverter PC
board.
YES
NO
NO
Does
the voltage
between terminals
P2(or P3) and N3 gradually
rise to 556 VDC (Y1)
after turning
on?
Monitor field power
supply.
Replace the inverter
PC board.
The voltage
between the P2
(or P3) and N3 terminals
is 380 VDC (Y1) or
more when the
compressor is
running.
Does K2
turn on?
Is
the voltage of
power supply
380~415V?
YES
NO
Is
220 ~ 240 V
at the connector X1A of
outdoor PC board
(A1P) side?
Check the transmission
wiring between the
outdoor unit PC board
and inverter unit.
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.