Daikin RXYQ10MY1K [65/310] Basic control

Daikin RXYQ10MY1K [65/310] Basic control
Basic Control Si39-502A
54 Function
2. Basic Control
2.1 Normal Operation
2.1.1 List of Functions in Normal Operation
Part Name Symbol
(Electric
Symbol)
Function of Functional Part
Normal Cooling Normal Heating
Compressor (M1C, M2C)
PI control, High pressure
protection, Low pressure
protection, Td protection,
INV protection
PI control, High pressure
protection, Low pressure
protection, Td protection,
INV protection
Outdoor unit fan (M1F) Cooling fan control Step 7 or 8
Four way valve 20S1 (Y1R) OFF ON
Main motorized valve EV1 (Y1E) 2000 pls PI control
Subcool heat exchanger
electronic expansion valve
EV2 (Y2E) PI control 0 pls
Hot gas bypass valve SVP (Y1S) OFF
Energized when the system is set
to low pressure control mode
Receiver gas discharging
valve
SVG (Y4S) OFF OFF
Non-operating unit liquid
pipe stop valve
SVSL (Y6S) ON ON