Daikin RZP100DVAL [103/255] Pump down residual operation

Daikin FAYP100BV1 [103/255] Pump down residual operation
Function Details SiE25-110
94 Function and Operation
[Defrost control]
[Defrost ending condition]
Defrosting ends when the following conditions have been realized after 1 minute elapsed from
defrosting start. Note that defrosting can be operated for 10 minutes at longest.
4.2.25 Pump down residual operation
Conducts pump down residual operation when compressor stops to collect refrigerant in
evaporator for preventing liquid refrigerant from remaining in the evaporator.
[Contents of control]
Compressor:For RZP71D; 41 Hz
For RZP100~140D; 110 Hz
Motorized valve: 0 pls (fixed opening degree)
Solenoid valve for receiver gas purging (SVG): ON (open)
[Ending condition]
Model RZP71D Model RZP100~140D
AHz 172Hz 210Hz
BHz 134Hz 177Hz
CHz 48Hz 74Hz
D pls 95 pls
95 pls (RZP100D)
135 pls (RZP125D)
154 pls (RZP140D)
A Hz
ON
OFF
ON
ON
OFF
ON
ON
ON
OFF
ON
B Hz
C Hz
D pls
480 pls
D pls
Previous control
Compressor
4-way valve
Motorized valve
Outdoor unit fan
Indoor fan
Solenoid valve (SVG)
Defrosting completeDefrosting start
(S2557)
Outdoor unit heat exchanger outlet temperature (Tb)10˚C
High pressure (Hp)2.16 MPa
OR
(S2558)
30 seconds elapsed with residual operation
LP<0.1 MPa (when cooling)
LP<0.02 MPa (when heating)
OR
(S2561)