Daikin RZP100DVAL [141/255] Outdoor unit

Daikin FHYP60BV1 [141/255] Outdoor unit
Troubleshooting by Remote Controller Display / LED Display SiE25-110
132 Troubleshooting
Outdoor Unit
Note: 1. Possibility of open phase in power supply.
2. In RZP model, L8 is not displayed on remote controller. Please see page 167 for more detail.
Outdoor
Unit
Malfunction
Outdoor unit LED
Display
Remote
Controller
Display
Location of Malfunction Contents of Malfunction
Details of
Malfunction
(Reference
Page)
A 1234 Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Controller
54333
E0 ——Activation of protection
device Note 1.
148
5
———— E1 ——Outdoor unit P.C board
malfunction
149
54333
E3 ——Abnormality of high
pressure (HPS)
150
94333
E4 ——Abnormality of low
pressure (outdoor)
152
94333
E5 ——Compressor motor lock
malfunction
153
93344
E7  Outdoor fan motor lock or
outdoor fan instantaneous
overcurrent malfunction
155
53333
E9 ——Malfunction of Electronic
expansion valve
156
54333
F3 ——Discharge pipe
temperature malfunction
158
54433
H3 ——Faulty high pressure switch
(HPS)
160
54433
H7 ——Malfunction of outdoor fan
signal
161
54433
H9 ——Malfunction of outdoor air
temperature sensor system
162
54433
J3 ——Malfunction of discharge
pipe temperature sensor
system
162
94433
J5 ——Suction pipe thermistor
malfunction
162
54433
J6 ——Malfunction of heat
exchanger temperature
sensor system
162
54433
JC ——Suction pipe pressure
sensor malfunction
163
53334
L4 ——High temperature of
radiation fin
164
53343
L5 ——Overcurrent of DC output
(instantaneous)
165
53444
(L8)
Note 2
——Electronic thermal switch
(time lag)
167
54444
L9 ——Stall prevention (time lag) 169
————— LC ——Malfunction of transmission
system (between control
PCB and inverter PCB)
171
94334
P1 ——Open phase or voltage
unbalance
173
54433
P4 ——Faulty radiation fin
temperature sensor
175,176
5
———— PJ ——Error in capacity setting 177

Содержание

Скачать