Daikin RZP100DVAL [110/255] Optimal operation condition

Daikin RZP125DV1 [110/255] Optimal operation condition
SiE25-110 Maintenance Inspections
Troubleshooting 101
1. Maintenance Inspections
1.1 Optimal Operation Condition
Guide Lines for
Optimal
Operation
Condition
The operation value guide lines when operating under standard conditions (at Rated
frequency) by pushing the test run button on the remote controller are as given in the table
below. RZ(Y)71~125L are used as example outdoor units in the table.
Indoor Unit Fan: “H” Operation Compressor: Rated Frequency
Note: Figures given inside parentheses are in unit of kg/cm²
Standard Conditions
During or after maintenance, when the power supply is turned back on, operation restarts
automatically by the “auto restart function.” Please exercise the proper caution.
High
Pressure
(Mpa)
Low
Pressure
(Mpa)
Discharge
Pipe
Temperature
(˚C)
Suction
Temperature
(˚C)
Indoor Unit
Side:
Differential
Between
Suction
Temperature
and
Discharge
Temperature
(˚C)
Outdoor Unit
Side:
Differential
Between
Suction
Temperature
and
Discharge
Temperature
(˚C)
Cooling 50Hz 1.62~2.11
(16.5~21.5)
0.39~0.59
(4.0~6.0)
60~95 0~14 8~18 7~12
60Hz 1.72~2.21
(17.5~22.5)
0.34~0.54
(3.5~5.5)
70~115 –2~10
Heating 50Hz 1.42~2.06
(14.5~21.0)
0.29~0.44
(3.0~4.5)
55~95 –4~4 14~30 2~6
60Hz 1.62~2.11
(16.5~21.5)
0.29~0.44
(3.0~4.5)
60~115 –6~2
Indoor Unit Conditions Outdoor Unit Conditions
Cooling Operation 27˚C DB/19˚C WB 35˚C DB
Heating Operation 20˚C DB 7˚C DB/6˚C WB