Daikin RZP100DVAL [72/255] Emergency operation

Daikin FHYCP100DVE [72/255] Emergency operation
SiE25-110 Existence of DIP Switch, Jumper and BS
Field Setting 63
3.3 Emergency Operation
Emergency
Operation of
Indoor Units
You can operate the system manually by changing the setting of the emergency switch (SS1)
on the indoor unit’s PC board from “Normal” to “Emergency.” When switched however the
equipment cannot regulate temperature. The table below contains a list by model of actuators
for manually operating indoor units in time of emergency.
Method of switching in time of emergency
Notes: 1. Do not operate from remote controller during emergency operation.
2. Operate the switch only when the power supply is turned OFF.
Emergency
Operation of
Outdoor Units
Turn off the power supply and set the emergency switch to ON and “Heat” for heating or “Cool”
for cooling. Operation will be started manually when you turn the power back on. (“Heat” cannot
be set for a cooling only air-conditioner.)
Concerning
Emergency
Operation
If a safety device should be actuated during emergency operation, all actuators are turned OFF.
If you reset after waiting for 3 minutes, operation will start again. Emergency operation cannot
be carried out if the PC board itself is defective.
Note: For emergency operation, be sure to set emergency operation for both the indoor and outdoor
units. Do not attempt to operate the equipment from the remote controller during emergency
operation. Emergency operation is computer-controlled, and therefore cannot be carried out if
the microcomputer is not operating properly.
The table below contains a list of actuators for manually operating the equipment in time of
emergency.
During emergency heating operation, defrosting is carried out for 3 minutes every hour. (4-way
valve, outdoor unit fan and indoor unit fan are turned OFF.)
Model Fan Drain Raising
FHYCP 
FUYP 
FHYP  (OPTION)
FAYP
ON
COOL
ON
COOL
ON
COOL
OFF HEAT OFF HEAT OFF HEAT
COOL
or
HEAT
FORCED
COOLING
FACTORY SET
FORCED
HEATING
DS1 SETTING
(S1953)
Actuator Cooling Heating
Compressor ON ON
4-WAY VALVE OFF ON
Indoor Unit Fan H Fan Speed H Fan Speed
Drain Pump ON ON