Daikin RZP100DVAL [175/255] Troubleshooting

Daikin FHYCP100DVL [175/255] Troubleshooting
Troubleshooting by Remote Controller Display / LED Display SiE25-110
166 Troubleshooting
Troubleshooting
YES
NO
Replace the compressor.
NO
Replace the inverter PC board.
Compressor inspection
Inspect according to the diagnosis
procedure for abnormal noise,
vibration, operating status, etc.
of the compressor.
Correct the power supply.
YES
YES
NO
0
Approximate value
RZP71DV1
RZP71DVAL
RZP100 ~ 140DV1
RZP100DVAL
RZP125DTAL
RZP140DTAL
Instantaneous overcurrent
detection value
20A
65A
65A
Is
instantaneous voltage
drop generated?
Is
the compressor
coil disconnected or
is the insulation
defective?
NO
YES
Open the stop valve.
Is the stop valve open?
Turn the main power supply
off, and then disconnect the
connection between the
compressor and inverter.
Check the installation
conditions.
Check the power
supply voltage.
Continuity check in the
power transistor (IGBT)Is
the continuity
normal?
NO
Replace the inverter PC board.
YES
Is
the inverter
output voltage
generated
approximately at the
same increasing speed
for each phase after
turning on again?
(*) (U-V, V-W,
W-U)
*
When operating compressor
with compressor output line
disconnected, the compressor
stops due to malfunction after
elapsed time of 5 seconds.
Therefore, check the voltage
increase for 5 seconds.
Check No. 10
(S2592)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.