Daikin RZP100DVAL [181/255] Troubleshooting

Daikin FHYP45BV1 [181/255] Troubleshooting
Troubleshooting by Remote Controller Display / LED Display SiE25-110
172 Troubleshooting
Troubleshooting
NO
Connect the transmission
wiring, and turn on again.
Connect the connector, and
turn on again.
YES
YES
Fix the disconnection, and
turn on again.
NO
NO
Replace the fan motor.
Inverter transmission
malfunctioned due to the
malfunction of fan motor.
NO
Replace the control PC
board.
Replace the inverter PC
board.
Check for faulty connector
connection in the transmission wiring
and for clamps with high tension line.
YES
YES
Is
the fan motor connector
connected?
Is the
transmission wiring
between the control and
inverter PC board
disconnected?
(*2)
YES
NO
Is “E7”
displayed on the
remote controller?
(“LC” is not
displayed?)
NO
YES
Are
connectors
connecting the control
and inverter PC board
connected securely?
(*1)
Is the
microcomputer normal
monitor (green) on inverter
PC board blinking?
Is the
microcomputer
normal LED on control
PC board blinking?
*1: Applicable models are RZP71D.
*2: Applicable models are RZP71D.
Disconnect
the fan motor connector,
and turn on again.
(S2595)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.