Daikin RZP100DVAL [124/255] Equipment operates but does not provide heating

Daikin FHYCP125DVE [124/255] Equipment operates but does not provide heating
SiE25-110 Troubleshooting Based on Equipment Condition
Troubleshooting 115
3.7 Equipment Operates but does not Provide Heating.
Applicable Model All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Possible Cause
Excess charge of refrigerant
Air intrudes into refrigerant system
Faulty pressure switch
Faulty magnetic switch for outdoor unit fan motor
Faulty aux. relay for outdoor unit fan motor
Soiled heat exchanger of outdoor unit
There is an interfering item in air flow of outdoor unit
Malfunction of outdoor unit fan
Soiled air filter of indoor unit
Soiled heat exchanger of indoor unit
There is some interfering item in airflow of indoor unit
Malfunction of indoor unit fan
Troubleshooting
Measure the temperature of
suction air and supply air.
Temperature difference =
Suction air temp. – Supply air
temp.
Wait for a while.
No abnormality
No abnormality
Additional unit installation
should be considered
After vacuum drying, charge
correct amount of refrigerant.
Check each item
Check each item
Check each item
Temperature
difference for heating
should be between 14
and 30˚C.
Is the unit
in defrost mode?
Is the operation
current less than specified
level?
Does the
heat load increase after
installation of the
unit?
YES
YES
YES
YES
YES
YES
Incorrect selection of model
Affection of sunlight
Affection of excessive fresh
air into room
Gas shortage possibly
generates trouble.
Clogged air filter
Soiled heat exchanger
Malfunction of indoor fan
motor (Refer error code “A6”)
Refrigerant overcharge
Soiled heat exchanger
Short circuit of discharge air
Disturbing item in air flow
Malfunction of fan motor of
outdoor unit
(Refer error code “E7”, “H7”)
Insufficient compression of
compressor
Insufficient circulation of
refrigerant
Faulty expansion valve
NO
NO
NO
Does indoor
unit air flow
rate down?
NO
Is the level
of high pressure lower
than normal level?
NO
NO
(S1995)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.