SiE25-110 Function Details
Function and Operation 97
C. Setting by capacity precedence
When setting dip switches DS1-4 on the outdoor unit PC board to ON, activates capacity
precedence setting in both A and B. If the air conditioning load increases, the low noise
operation stops to return to normal operation.
When setting the dip switches DS1-4 to OFF, precedes the low noise operation. Even if the air
conditioning load increases, the low noise operation continues.
Since the night time judgement (22-8 o’clock) is made in accordance with outside
temperature, the night time is a target only.
Emergency
Operation
Transmission between indoor and outdoor units is not conducted.
In cooling operation, ON for 20 minutes and OFF for 10 minutes are conducted in
succession.
In heating operation, defrosting is conducted once every 1 hour (for 3 minutes).
In other conditions than the above-mentioned, the same control as normal control is
conducted.
Low noise setting
(DS1-3)
Capacity
precedence setting
(DS1-4)
Operation of outdoor unit
OFF
OFF
Carries out low noise operation only when short circuit
between Contact T
1
and T
2
of X1M.
ON
Carries out low noise operation only when short circuit
between Contact T
1
and T
2
of X1M, but if the air
conditioning load increases, returns to normal operation.
ON
OFF
Carries out low noise operation when short circuit
between Contact T
1
and T
2
of X1M and at night (22-8
o’clock).
ON
Carries out low noise operation when short circuit
between Contact T
1
and T
2
of X1M and at night (22-8
o’clock),but if the air conditioning load increases, returns
to normal operation.