Daikin RZP100DVAL [119/255] Troubleshooting

Daikin RZP100DVAL [119/255] Troubleshooting
Troubleshooting Based on Equipment Condition SiE25-110
110 Troubleshooting
Troubleshooting
YES
YES
YES
NO
NO
YES
Normal.
(Thermostat OFF by
outdoor temperature)
Tur n on the power
switch or replace fuse.
NO
NO
YES
Replace the magnetic
switch or power
transistor.
Replace the PC board.
Replace the
compressor.
Check the thermistor.
NO
Air sensor
Indoor unit
PC board
Outdoor unit
PC board
Relay
Magnetic
switch
COMP
Input
to PC
board
Input
to PC
board
Output
from
PC
board
Output from
relay or
microcomputer
Output from
magnetic
switch or SW
circuit of
power
transistor
Output from
magnetic
switch or
U,V,W of
power
transistor
· Indoor unit fan runs at set airflow rate.
· (In cooling operation)
When air thermistor ambient temperature is higher than set temperature
· (In heating operation)
When air thermistor ambient temperature is lower than set temperature
Is the power
switch OFF or the fuse for
power switch
blown?
Is rated voltage
output from the magnetic
switch or power
transistor?
Is rated voltage output
from the PC board?
Is the heating
switch turned on at outdoor
temperature 27˚C
Is rated voltage
applied at
the compressor
terminals?
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(S2576)