Daikin RZP100DVAL [160/255] Troubleshooting

Daikin RZP125DV1 [160/255] Troubleshooting
SiE25-110 Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 151
Troubleshooting
Notes: Some models are not equipped with protection or control HPS.
Replace HPS with no continuity.
Correct the high pressure.
Replace the outdoor unit PC board.
Replace the high pressure switch (HPS).
NO
YES
Connect correctly.
NO
YES
Open the stop valve.
NO
YES
Is high pressure
abnormally high?
YES
NO
YES
NO
Check the installation
conditions.
Check No. 5
Is the stop
valve open?
Turn off the power supply.
Wait for 10 minutes after
compressor stops
operating, then check the
following.
Is there
continuity in
control and protection
HPS?
Set the remote controller
and turn on again.
Is the
malfunction code of
“H3” displayed?
Are
control and
protection HPS
connected to
outdoor unit PC
board?
(Note)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(S2582)