Daikin RZP100DVAL [142/255] System

Daikin RZP125DV1 [142/255] System
SiE25-110 Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 133
System
Outdoor
Unit
Malfunction
Outdoor unit LED
Display
Remote
Controller
Display
Location of Malfunction Contents of Malfunction
Details of
Malfunction
(Reference
Page)
A 1234 Other
than PC
Board
PC Board
Outdoor
Unit
Indoor
Unit
Remote
Controller
————— U0 ——Gas shortage 178
54334
U2 ——Insufficient voltage 179
93833
U2 ——Open phase or main circuit
capacitor malfunction
179
————— U4
or UF
—Transmission error
(between indoor and
outdoor unit)
181
————— U5 Transmission error
(between indoor and
remote controller)
183
————— U8 Transmission error
between “main” remote
controller and “sub” remote
controller
184
————— UA Excessive indoor units
connected to this system.
185
————— UC —— Centralized address setting
error
187

Содержание