Daikin RZP100DVAL [171/255] Malfunction of thermistor system

Daikin FHYCP71DVE [171/255] Malfunction of thermistor system
Troubleshooting by Remote Controller Display / LED Display SiE25-110
162 Troubleshooting
6.24 Malfunction of Thermistor System
Remote
Controller
Display
H9,J3,J5,J6
Outdoor Unit LED
Display
Refer to P.132
Applicable
Models
RZP71~140D
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by each individual thermistor.
Malfunction
Decision
Conditions
When thermistor is disconnected or short-circuited during operation
Supposed
Causes
Faulty thermistor
Faulty connection of connector
Faulty outdoor unit PC board (control PC board)
Troubleshooting
YES
YES
Normal?
Connect correctly.
Replace the outdoor unit PC board
(control PC board).
NO
Check connectors for
connection.
Remove thermistor from
outdoor unit PC board,
then measure the
resistance using a tester.
H9 : Malfunction of outdoor temperature thermistor system
J3 : Malfunction of discharge pipe thermistor system
J5 : Malfunction of suction pipe thermistor system
J6 : Malfunction of heat exchange thermistor
Normal?
Replace the thermistor.
NO
(S2589)
0
See Check No. 12 for “Thermistor temperature/Resistance characteristics”.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.