Delta Electronics VFD037CH23A-21 — руководство по настройке и устранению неполадок для устройств [139/638]

Превью страниц Страница 139 / 638
Delta Electronics VFD037CH23A-21 [139/638] Troubleshooting
Chapter 8 Optional Cards
8-17
Basic Registers
BR# R/W Content Explanation
#0 R
Model name Set up by the system; read only. The model code of
CMC-MOD01=H’0203
#1 R
Firmware
version
Displaying the current firmware version in hex, e.g. H’0100 indicates the
firmware version V1.00.
#2 R
Release date of
the version
Displaying the data in decimal form. 10,000s digit and 1,000s digit are for
“month”; 100s digit and 10s digit are for “day”.
For 1 digit: 0 = morning; 1 = afternoon.
#11 R/W Modbus Timeout Pre-defined setting: 500 (ms)
#13 R/W Keep Alive Time Pre-defined setting: 30 (s)
LED Indicator & Troubleshooting
LED Indicators
LED Status Indication How to correct it?
On Power supply in normal status --
POWER Green
Off No power supply Check the power supply
On Network connection in normal status --
Flashes Network in operation --
LINK Green
Off Network not connected Check if the network cable is
connected
Troubleshooting
Abnormality Cause How to correct it?
AC motor drive not powered
Check if AC motor drive is powered, and if the
power supply is normal.
POWER LED off
CMC-MOD01 not connected
to AC motor drive
Make sure CMC-MOD01 is connected to AC motor
drive.
CMC-MOD01 not connected
to network
Make sure the network cable is correctly connected
to network.
LINK LED off
Poor contact to RJ-45
connector
Make sure RJ-45 connector is connected to
Ethernet port.
CMC-MOD01 not connected
to network
Make sure CMC-MOD01 is connected to network.
No module found
PC and CMC-MOD01 in
different networks and
blocked by network firewall.
Search by IP or set up relevant settings by AC
motor drive keypad.
CMC-MOD01 not connected
to network
Make sure CMC-MOD01 is connected to the
network.
Incorrect communication
setting in DCISoft
Make sure the communication setting in DCISoft is
set to Ethernet.
Fail to open
CMC-MOD01
setup page
PC and CMC-MOD01 in
different networks and
blocked by network firewall.
Conduct the setup by AC motor drive keypad.
Able to open
CMC-MOD01
setup page but fail
to utilize webpage
Incorrect network setting in
CMC-MOD01
Check if the network setting for CMC-MOD01 is
correct. For the Intranet setting in your company,
please consult your IT staff. For the Internet setting
in your home, please refer to the network setting

Содержание