Delta Electronics VFD037CH23A-21 [194/638] Pr explanation settings factory setting

Превью страниц Страница 194 / 638
Delta Electronics VFD110CH23A-21 [194/638] Pr explanation settings factory setting
Chapter 11 Summary of Parameter SettingsCH2000 Series
11-13
03 Analog Input/Output Parameters
Pr. Explanation Settings
Factory
Setting
03-00 Analog Input Selection (AVI) 0: No function 1
03-01 Analog Input Selection (ACI)
1: Frequency command (speed limit under torque
control mode)
0
03-02 Analog Input Selection (AUI) 2: Torque command (torque limit under speed mode) 0
3: Torque compensation command
4: PID target value
5: PID feedback signal
6: PTC thermistor input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive/negative torque limit
11: PT100 thermistor input value
12: Reserved
13: PID Offset (%) (h.)
14~17: Reserved
03-03 Analog Input Bias (AVI)
-100.0~100.0%
0
03-04 Analog Input Bias (ACI)
-100.0~100.0%
0
03-05
Analog Positive Voltage Input
Bias (AUI)
-100.0~100.0%
0
03-06 Reserved
03-07
Positive/negative Bias Mode
(AVI)
03-08
Positive/negative Bias Mode
(ACI)
03-09
Positive/negative Bias Mode
(AUI)
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving
as the center
4: Serve bias as the center
0
03-10
Analog Frequency Command
for Reverse Run
0: Negative frequency is not valid. Forward and
reverse run is controlled by digital keypad or
external terminal.
1: Negative frequency is valid. Positive frequency =
forward run; negative frequency = reverse run.
Direction can not be switched by digital keypad or
external terminal control.
0
03-11 Analog Input Gain (AVI)
-500.0~500.0%
100.0
03-12 Analog Input Gain (ACI)
-500.0~500.0%
100.0
03-13 Analog Positive Input Gain (AUI)
-500.0~500.0%
100.0
03-14
Analog Negative Input Gain
(AUI)
-500.0~500.0%
100.0
03-15 Analog Input Filter Time (AVI)
0.00~20.00 sec.
0.01
03-16 Analog Input Filter Time (ACI)
0.00~20.00 sec.
0.01
03-17 Analog Input Filter Time (AUI)
0.00~20.00 sec.
0.01
03-18
Addition Function of the Analog
Input
0: Disable (AVI, ACI, AUI)
1: Enable
0

Содержание