Delta Electronics VFD750CH23A-00/-21 [399/638] S rad w p m n t
Chapter 12 Description of Parameter SettingsCH2000 Series
12-183
position time will be.
10-00
10-01
RUN
MI=d35
MO=d39
10-19
11-25
11-26
PG feedback
Output frequency
Time
Max. Torque Command
Factory Setting: 100
Settings 0~500%
The upper limit of torque command is 100%.
Calculation equation for motor rated torque:
motor rated torque:
)/(
)(
).(
srad
WP
MNT
; P(W) value= Pr.05-02;
ω(rad/s) value= Pr.05-03
srad
RPM
/
60
2
Source of Torque Offset
Factory Setting: 0
Settings 0: Disable
1: Analog input (Pr.03-00)
2: Torque offset setting (Pr.11-29)
3: Control by external terminal (by Pr.11-30 to Pr.11-32)
This parameter is the source of torque offset.
When it is set to 3, source of torque offset would determine Pr.11-30 to Pr.11-32 by
When it is set to 3, the source of torque offset will regard Pr.11-30~11-32 by the multi-function
input terminals (MI) setting (31, 32 or 33).
N.O. switch status: ON= contact closed, OFF= contact open
Pr. 11-32 Pr. 11-31 Pr. 11-30
MI=33(High) MI=32(Mid) MI=31(Low) Torque Offset
OFF OFF OFF None
OFF OFF ON 11-30
OFF ON OFF 11-31
OFF ON ON 11-30+11-31
ON OFF OFF 11-32
ON OFF ON 11-30+11-32
ON ON OFF 11-31+11-32
ON ON ON 11-30+11-31+11-32