Chapter 11 Summary of Parameter Settings CH2000 Series
11-22
Pr. Explanation Settings
Factory
Setting
53: Reserved
54: Communication error (CE1)
55: Communication error (CE2)
56: Communication error (CE3)
57: Communication error (CE4)
58: Communication Time-out (CE10)
59: PU Time-out (CP10)
60: Brake transistor error (bF)
61: Y-connection/-connection switch error (ydc)
62: Decel. Energy Backup Error (dEb)
63: Slip error (oSL)
64: Electromagnet switch error (ryF)
65 : PG Card Error (PGF5)
66-72: Reserved
73: External safety gate S1
74~78: Reserved
79: U phase over current (Uocc)
80: V phase over current (Vocc)
81: W phase over current (Wocc)
82: U phase output phase loss (OPHL)
83: V phase output phase loss (OPHL)
84: W phase output phase loss (OPHL)
85: PG-02U ABZ hardware disconnection
86: PG-02U UVW hardware disconnection
87~89: Reserved
90: Inner PLC function is forced to stop
100: Reserved
101: CANopen software disconnect1 (CGdE)
102: CAN open software disconnect2 (CHbE)
103: CANopen synchronous error (CSYE)
104: CANopen hardware disconnect (CbFE)
105: CANopen
index setting error (CIdE)
106: CANopen
slave station number setting error
(CAdE)
107: CANopen
index setting exceed limit (CFrE)
111: Internal communication overtime error(InrCOM)
06-23 Fault Output Option 1
0~65535(refer to bit table for fault code)
0
06-24 Fault Output Option 2
0~65535(refer to bit table for fault code)
0
06-25 Fault Output Option 3
0~65535(refer to bit table for fault code)
0
06-26 Fault Output Option 4
0~65535(refer to bit table for fault code)
0
06-27
Electronic Thermal Relay
Selection 2 (Motor 2)
0: Inverter motor
1: Standard motor
2: Disable
2
06-28
Electronic Thermal
Characteristic for Motor 2
30.0~600.0 sec
60.0
06-29 PTC Detection Selection
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0
06-30 PTC Level
0.0100.0%
50.0
06-31
Frequency Command for
Malfunction
0.00~655.35 Hz
Read
only
06-32 Output Frequency at Malfunction
0.00~655.35 Hz
Read
only
06-33 Output Voltage at Malfunction
0.0~6553.5 V
Read
only