Chapter 15 CANopen Overview C2000 Series
15-19
15-3-5 DI/DO AI AO are controlled via CANopen
To control the DO AO of the motor drive through CANopen, follow the steps below:
1. To set the DO to be controlled, define this DO to be controlled by CANopen. For example, set
Pr02-14 to control RY2.
2. To set the DO to be controlled, define this AO to be controlled by CANopen. For example, set
Pr03-23 to control AFM2.
3. To control the mapping index of CANopen. If you want to control DO, then you will need to control
Index2026-41. If you want to control AO, then you will need to control 2026-AX. If you want to set
RY2 as ON, set the bit 1 of Index 2026-41 =1, then RY2 will output 1. If you want to control AFM2
output = 50.00%, then you will need to set Index 2026-A2 =5000, then AFM2 will output 50%.
Mapping table of CANopen DI DO AI AO:
DI:
Terminal Related Parameters R/W Mapping Index
FWD == RO 2026-01 bit 0
REV == RO 2026-01 bit 1
MI 1 == RO 2026-01 bit 2
MI 2 == RO 2026-01 bit 3
MI 3 == RO 2026-01 bit 4
MI 4 == RO 2026-01 bit 5
MI 5 == RO 2026-01 bit 6
MI 6 == RO 2026-01 bit 7
MI 7 == RO 2026-01 bit 8
MI 8 == RO 2026-01 bit 9
MI 10 == RO 2026-01 bit 10
MI 11 == RO 2026-01 bit 11
MI 12 == RO 2026-01 bit 12
MI 13 == RO 2026-01 bit 13
MI 14 == RO 2026-01 bit 14
MI 15 == RO 2026-01 bit 15
DO
Terminal Related Parameters R/W Mapping Index
RY1 P2-13 = 50 RW 2026-41 bit 0
P2-14 = 50 RW 2026-41 bit 1
RY2
P2-15 = 50 RW 2026-41 bit 2
MO1 P2-16 = 50 RW 2026-41 bit 3
MO2 P2-17 = 50 RW 2026-41 bit 4
MO3 P2-18 = 50 RW 2026-41 bit 5
MO4 P2-19 = 50 RW 2026-41 bit 6