Chapter 12 Description of Parameter SettingsCH2000 Series
12-7
This parameter determines the control method of the AC motor drive:
0: (IM V/f control): user can design proportion of V/f as required and can control multiple motors
simultaneously.
1: (IM V/f control + Encoder): user can use optional PG card with encoder for the closed-loop
speed control.
2: (IM Sensorless vector control): get the optimal control by the auto-tuning of motor
parameters.
3: (IM FOC vector control+ encoder): besides torque increases, the speed control will be more
accurate (1:1000).
4: (PM FOC vector control + Encoder): besides torque increases, the speed control will be more
accurate (1:1000).
5: FOC Sensorless: IM field oriented sensorless vector control
6: PM Sensorless (PM field oriented sensorless vector control)
When setting Pr.00-11 to 0, the V/F control diagram is shown as follows.
Fcmd
Pr00-20
2/3
e->s
AVR
07-23
3/2
s->e
IGBT
PWM
01-00
01-01
01-02
05-01
05-02
05-03
05-04
DC BUS
V/F
table
Voltage
Detect
Protection
accel/decel time
DC BUS Voltage
Current Detection
01-00,01-01
01-02,01-03
01-04,01-05
01-06,01-07
01-08
Top Limit F:01-10
Lower Limit F:01-11
Torque
Compensate
07-26
Filter
Time
07-24
Vcmd
M
When setting Pr.00-11 to 1, the V/F control + encoder diagram is shown as follows.
Irms
M
IGBT
PWM
V/F
table
07-26
Filter
Time
07-24
Fcmd
EN
Voltage
cmd
Power
Factor
X
+
Filter Time
Frequency
Inaccuracy
Voltage
Command
+
Fcmd
00-20
Frequency
Inaccuracy
Current
Detect
Voltage Compensate
Slip
comp.
Real Speed
Real Speed