Delta Electronics VFD037CH23A-21 — настройки параметров для управления переменным током [238/638]

Превью страниц Страница 238 / 638
Delta Electronics VFD037CH23A-21 [238/638] Group 1 basic parameters
Chapter 12 Description of Parameter SettingsCH2000 Series
12-22
Group 1 Basic Parameters This parameter can be set during operation.
Maximum Output Frequency
Factory Setting: 60.00/50.00
Settings 50.00~600.00Hz
This parameter determines the AC motor drive’s Maximum Output Frequency. All the AC motor
drive frequency command sources (analog inputs 0 to +10V, 4 to 20mA, 0 to 20mAand ±10V) are
scaled to correspond to the output frequency range.
Output Frequency of Motor 1base frequency and motor rated frequency
Output Frequency of Motor 2base frequency and motor rated frequency
Factory Setting: 60.00/50.00
Settings 0.00~600.00Hz
This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. If the motor is 60Hz, the setting should be 60Hz. If the motor is 50Hz, it should be set to
50Hz.
Output Voltage of Motor 1base frequency and motor rated frequency
Output Voltage of Motor 2base frequency and motor rated frequency
Factory Setting: 200.0/400.0
Settings 230V series: 0.0~255.0V
460V series: 0.0~510.0V
This value should be set according to the rated voltage of the motor as indicated on the motor
nameplate. If the motor is 220V, the setting should be 220.0. If the motor is 200V, it should be set to
200.0.
There are many motor types in the market and the power system for each country is also difference.
The economic and convenience method to solve this problem is to install the AC motor drive. There
is no problem to use with the different voltage and frequency and also can amplify the original
characteristic and life of the motor.
Mid-point Frequency 1 of Motor 1
Factory Setting: 3.00
Settings 0.00~600.00Hz
Mid-point Voltage 1 of Motor 1
Factory Setting: 11.0/22.0
Settings 230V series: 0.0~240.0V
460V series: 0.0~480.0V
Mid-point Frequency 1 of Motor 2
Factory Setting: 3.00
Settings 0.00~600.00Hz
Mid-point Voltage 1 of Motor 2

Содержание

1610

Узнайте, как правильно настроить параметры для управления переменным током, включая частоту и напряжение для различных типов моторов. Оптимизируйте работу вашего оборудования.