Chapter 11 Summary of Parameter SettingsCH2000 Series
11-27
08 High-function PID Parameters
Pr. Explanation Settings
Factory
Setting
08-00 Input Terminal for PID Feedback
0: No function
1: Negative PID feedback: on analogue input acc. To
setting 5 of Pr. 03-00 to Pr.03-02.
2: Negative PID feedback from PG card (Pr.10-15, skip
direction)
3: Negative PID feedback from PG card (Pr.10-15)
4: Positive PID feedback from external terminal AVI
(Pr.03-00)
5: Positive PID feedback from PG card (Pr.10-15, skip
direction)
6: Positive PID feedback from PG card (Pr.10-15)
7: Negative PID feedback from communication
protocol
8: Positive PID feedback from communication protocol
0
08-01 Proportional Gain (P)
0.0~500.0%
1.0
08-02 Integral Time (I)
0.00~100.00sec
1.00
08-03 Derivative Control (D)
0.00~1.00sec
0.00
08-04 Upper Limit of Integral Control
0.0~100.0%
100.0
08-05 PID Output Frequency Limit
0.0~110.0%
100.0
08-06
PID feedback value by
communication protocol
0.00~200.00% 0.00
08-07 PID Delay Time
0.0~2.5 sec
0.0
08-08 Feedback Signal Detection Time
0.0~3600.0 sec
0.0
08-09
Feedback Signal Fault
Treatment
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
0
08-10 Sleep Reference Point
0.00 ~ 600.00Hz
0.00
08-11 Wakeup Reference Point
0.00 ~ 600.00Hz
0.00
08-12 Sleep Time
0.0 ~ 6000.0sec
0.0
08-13 PID Deviation Level
1.0 ~ 50.0%
10.0
08-14 PID Deviation Time
0.1~300.0sec
5.0
08-15 Filter Time for PID Feedback
0.1~300.0sec
5.0
08-16 PID Compensation Selection
0: Parameter setting
1: Reserved
0
08-17 PID Compensation -100.0~+100.0% 0
08-18 Setting of Sleep Mode Function
0: Follow PID output command
1: Follow PID feedback signal
0
08-19 Wakeup Integral Limit 0.0~200.0% 50.0
08-20 PID Mode Selection
0: Serial connection
1: Parallel connection
0
08-21
Enable PID to Change
Operation Direction
0: Operation direction can be changed
1: Operation direction can not be changed
0
08-22 Wakeup Delay Time 0.00~600.00 Seconds 0.00
08-23 PID Control Flag
Bit 0 = 1, PID reverse running must follow the setting of
Pr00-23.
Bit 0 = 0, PID reverse running follow PID’s calculated
value.
0.00