Delta Electronics VFD037CH23A-21 [207/638] Pr explanation settings factory setting

Превью страниц Страница 207 / 638
Delta Electronics VFD450CH23A-00/-21 [207/638] Pr explanation settings factory setting
Chapter 11 Summary of Parameter Settings CH2000 Series
11-26
Pr. Explanation Settings
Factory
Setting
07-21 Auto Energy-saving Operation
0: Disable
1: Enable
0
07-22 Energy-saving Gain
101000%
100
07-23
Auto Voltage Regulation(AVR)
Function
0: Enable AVR
1: Disable AVR
2: Disable AVR during deceleration
0
07-24
Filter Time of Torque
Compensation (V/F and SVC
control mode)
0.001~10.000 sec
0.020
07-25
Filter Time of Slip
Compensation (V/F and SVC
control mode)
0.001~10.000 sec
0.100
07-26
Torque Compensation Gain (V/F
and SVC control mode)
0~10
0
07-27
Slip Compensation Gain (V/F
and SVC control mode)
0.00~10.00
0.00
07-28 Reserved
07-29 Slip Deviation Level
0.0~100.0%
0
07-30 Detection Time of Slip Deviation
0.0~10.0 sec
1.0
07-31 Over Slip Treatment
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0
07-32 Motor Hunting Gain
0~10000
1000
07-33
Auto Reset Time for Restart
after Fault
0.0~6000.0 sec
60.0