Delta Electronics VFD037CH23A-21 [149/638] Troubleshooting

Превью страниц Страница 149 / 638
Delta Electronics VFD055CH23A-21 [149/638] Troubleshooting
Chapter 8 Optional Cards
8-27
Disconnecting CMC- EIP01 from VFD-CH2000
1. Switch off the power supply of VFD-CH2000.
2. Remove the two screws (see Figure 6).
3. Twist opens the card clip and inserts the slot type screwdriver to the hollow to prize the PCB off the
card clip (see Figure 7).
4. Twist opens the other card clip to remove the PCB (see Figure 8).
[Figure 6] [Figure 7]
[Figure 8]
LED Indicator & Troubleshooting
There are 2 LED indicators on CMC-EIP01. The POWER LED displays the status of power supply,
and the LINK LED displays the connection status of the communication.
LED Indicators
LED Status Indication How to correct it?
On Power supply in normal status --
POWER Green
Off No power supply
Check the power supply.
On
Network connection in normal
status
--
Flashes Network in operation
--
LINK Green
Off Network not connected
Check if the network cable is
connected.
Troubleshooting
Abnormality Cause How to correct it?
AC motor drive not powered
Check if AC motor drive is powered, and if the
power supply is normal.
POWER LED off
CMC-EIP01 not connected to
AC motor drive
Make sure CMC-EIP01 is connected to AC motor
drive.