Delta Electronics VFD037CH23A-21 — технические характеристики и условия эксплуатации для приводов [157/638]

Превью страниц Страница 157 / 638
Delta Electronics VFD750CH23A-00/-21 [157/638] Ul type i ip20
Chapter 9 Specifications
9-6
Protection Level Operating Environment
UL Type I / IP20
When the AC motor drive is operating at the rated
current and the ambient temperature has to be
between 10 ~ +40. When the temperature is
over 40, for every increase by 1, decrease 2%
of the rated current. The minimum allowable
temperature is 60.
UL Open Type /
IP20
When the AC motor drive is operating at the rated
current and the ambient temperature has to be
between -10 ~ +50. When the temperature is
over 50, for every increase by 1, decrease 2%
of the rated current. The minimum allowable
temperature is 60.
High Altitude
If AC motor drive is installed at altitude 0~1000m,
follow normal operation restriction. If it is install at
altitude 1000~3000m, decrease 2% of rated current
or lower 0.5 of temperature for every 100m
increase in altitude. Maximum altitude for Corner
Grounded is 2000m.