Delta Electronics VFD037CH23A-21 — настройки параметров для управления приводами: руководство [389/638]

Превью страниц Страница 389 / 638
Delta Electronics VFD110CH23A-21 [389/638] Reserved arm kp
Chapter 12 Description of Parameter SettingsCH2000 Series
12-173
FOC Gain of Excitation Current Rise Time
Factory Setting:100
Settings 33~100% Tr (Tr: rotor time constant)
This parameter sets the drive’s excitation current rise time when activates at senslorless torque
mode. When the drive’s activation time is too long at torque mode, please adjust this parameter to
a shorter time constant.
Top Limit of Frequency Deviation
Factory Setting: 20.00
Settings 0.00~100.00Hz
Pr.10-29 is for setting the maximum of frequency deviation.
When this parameter is set too large, resulting in abnormal PG feedback malfunction.
If customer application require a large Pr10-29 value, resulting in larger output slip, then it is tends
to be PG Error (PGF3, PGF4) in such a case. To prevent PGF3 and PGF4 error, set Pr10-10
Encoder Stall Level and to 10-13 Encoder Slip Range to be 0 "No function" (means removing
PGF3 and PGF4 detection). But this must only when the PG card connection and application are
correct, or prompt PG protection function will be disable. Too large Pr10-29 setting is not a
common set.
Resolver Pole Pair
Factory Setting: 1
Settings 1~50
To use Pr.10-30 function, user must set Pr.10-00=3(Resolver Encoder) first.
Reserved
ARM (Kp)
Factory Setting: 1
Settings 0~3
ARM (Ki)
Factory Setting: 1
Settings 0~3
Reserved
I/F Mode, current command
Factory Setting: 40
Settings 0~150%Irated (
Rated current % of the drive)
PM Sensorless Observer Bandwidth for High Speed Zone
Factory Setting: 5.00
Settings 0.00~600.00Hz