Chapter 12 Description of Parameter SettingsCH2000 Series
12-174
PM Sensorless Observer Low-pass Filter Gain
Factory Setting: 1.00
Settings 0.00~655.35Hz
PM Sensorless Control Word
Factory Setting: 0000
Settings 0000~FFFFh
Bit No. Function Description
0 Reserved
1 Reserved
2 Choose a control mode to start. 0 :Start by IF mode
1: Start by VF mode
3 Choose a mode to stop. 0 :Stop by IF mode
1 :Stop by VF mode
4 Reserved
5 Choose a control mode to stop 0 : When lower than Pr10-40, coast to stop
If lower than Pr10-40, decelerate to stop by VF mode.
6 Reserved
7 Reserved
Frequency Point when switch from I/F mode to PM Sensorless mode
Factory Setting: 20.00
Settings 0.00~600.00Hz
Frequency Point when switch from PM Sensorless Observation mode to I/F mode
Factory Setting: 20.00
Settings 0.00~600.00Hz
I/F mode, low pass-filter time
Factory Setting: 0.2
Settings 0.0~6.0 sec
Initial Angle Detection Time
Factory Setting: 5
Settings 0~20 ms
PM Sensorless Adjustment Procedure
1. When using high frequency standstill VFD parameter tuning, use VFD software to monitor
adjustment procedure. To download VFD Software go to:
http://www.delta.com.tw/product/em/download/download_main.asp?act=3&pid=1&cid=1&tpid=3
2. Testing PM High Frequency Standstill VFD (calculation of Rs, Ld, Lg)
Procedures:
A. Set control mode as VF mode (Pr00-10=0, Pr00-11=0
B.
Output Frequency of Motor 1 (Pr01-01)
C.
Output Voltage of Motor 1 (Pr01-02)
D.
Induction Motor and Permanent Magnet Motor Selection (Pr05-33=1)
E.
Full-load current of Permanent Magnet Motor(Pr05-34
F. Set Moto Auto Tuning Pr 05-00 =13;
High frequency and blocked rotor test for PM motor. Then