Delta Electronics VFD037CH23A-21 [332/638] When malfunction occurs use can check the current frequency command if it happens again it will overwrite the previous record
Chapter 12 Description of Parameter SettingsCH2000 Series
116
12-
PTC (Positive Temperature Coefficient) Detection Selection
Factory Setting: 0
Settings 0: Warn and keep operating
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
Pr.06-29 setting defines how the will drive operate after PTC detection. 再補充 03-00 d6
PTC Level
Factory Setting: 50.0
Settings 0.0~100.0%
It needs to set AVI/ACI/AUI analog input function Pr.03-00~03-02 to 6 (P.T.C. thermistor input
value).
It is used to set the PTC level, and the corresponding value for 100% is max. analog input value.
Frequency Command for Malfunction
Factory Setting: Read only
Settings 0.00~655.35Hz
When malfunction occurs, use can check the frequency command. If it happens again, it will
overwrite the previous record.
Output Frequency at Malfunction
Factory Setting: Read only
Settings 0.00~655.35Hz
When malfunction occurs, use can check the current frequency command. If it happens
again, it will overwrite the previous record.
Output Voltage at Malfunction
Factory Setting: Read only
Settings 0.0~6553.5V
When malfunction occurs, user can check current output voltage. If it happens again, it will
overwrite the previous record.
DC Voltage at Malfunction
Factory Setting: Read only
Settings 0.0~6553.5V
When malfunction occurs, user can check the current DC voltage. If it happens again, it will
overwrite the previous record.