Chapter 16 PLC Function CH2000 Series
16-63
API
30
ROR
P
D n
Rotate to the Right
Bit Devices Word Devices
X Y M K H KnX KnY KnM T C D
D
n
Operands:
D: if in KnY and KnM, only K4 (16-bit) is valid
n: n=K1~K16 (16-bit)
16 bit command (5 STEPS)
ROR
RORP
32-bit command
Flag signal: M1022 Carry flag
Explanation
1. D: Device to be rotated n: Number of bits to be rotated in 1 rotation
2. This instruction rotates the device content designated by D to the right for
n bits.
3. This instruction adopts pulse execution instructions (RORP).
Example
When X0 goes from Off to On, the 16-bit (4 bits as a group) in D10 will rotate to
the right, as shown in the figure below. The bit marked with will be sent to carry
flag M1022.
01110101 00111 001
010111001111001 0
0
upper bit lower bit
upper bit lower bit
*
X0
RORP
D10 K4
Rotate to the right
16 bits
Carry
flag
Carry
flag
After one rotation
to the right
D10
D10