Delta Electronics VFD055CH23A-21 [391/638] Zero load test
Chapter 12 Description of Parameter SettingsCH2000 Series
12-175
run the drive.
3. Set control mode as PM sensorless Mode (Parameters 00-10=0, 00-11=6)
4. Set VFD Parameters
Pr05-35 Rated Power of Permanent Magnet Motor
Pr05-36 Rated speed of Permanent Magnet Motor
Pr05-37 Pole number of Permanent Magnet Motor
Pr05-38 Inertia of Permanent Magnet Motor
5. Set ASR Parameters
Pr11-00 bit0=1: Auto tuning for ASR and APR
Pr11-02ASR1/ASR2 Switch Frequency, it is recommended to set Pr10-39 higher than
10Hz.
Pr11-03: ASR1 Low-speed Bandwidth and Pr11-03, ASR2 High-speed Bandwidth. Do not set
Low-speed Bandwidth too high to avoid dissipation of the estimator.
6. Set speed estimator and speed controls parameter.
Pr10-39 Frequency when switch from I/F Mode to PM sensorless mode.
Pr10-32 PM Sensorless Observer Bandwidth for High Speed Zone
7. Zero-load test
Refer to switch point procedure of I/F and FOC as shown in the image below.
Set frequency command
(Higher than switching command)
Perform RUN command
Yes
NO
Yes
NO
Big variation of current or
OC while switching
Lower Per Unit of System
Inertia (Pr.11-01)/
Lower ASR1 Low-speed
Bandwidth (Pr.11-03)
Can the drive run
normally until switching
to higher frequency?
Big variation of output
frequency or dissipation
Observe output current
fequency via
commnucation intrefac
e
/
Increase load and Test
Observe output current
fequency via
commnucation intreface
/
Procedure for switching between I
F mode and FOC mode
/
When running at high
frequency, is the frequency
stable?
IncreasePM Sensorless
Observer Bandwidth for
High Speed Zone (Pr.10-32)/
Decrease Per Unit of
System Inertia (Pr.11-01)