Delta Electronics VFD037CH23A-21 [190/638] Digital input output parameters

Превью страниц Страница 190 / 638
Delta Electronics VFD150CH23A-21 [190/638] Digital input output parameters
Chapter 11 Summary of Parameter SettingsCH2000 Series
11-9
02 Digital Input/Output Parameters
Pr. Explanation Settings
Factory
Setting
02-00 2-wire/3-wire Operation Control
0: 2-wire mode, power on for operation control
1: 2-wire mode 2, power on for operation control
2: 3-wire, power on for operation control
0
02-01
Multi-function Input Command 1
(MI1)
0: No function 1
02-02
Multi-function Input Command 2
(MI2)
1: Multi-step speed command 1/multi-step position
command 1
2
02-03
Multi-function Input Command 3
(MI3)
2: Multi-step speed command 2/multi-step position
command 2
3
02-04
Multi-function Input Command 4
(MI4)
3: Multi-step speed command 3/multi-step position
command 3
4
02-05
Multi-function Input Command 5
(MI5)
4: Multi-step speed command 4/multi-step position
command 4
0
02-06
Multi-function Input Command 6
(MI6)
5: Reset 0
02-07
Multi-function Input Command 7
(MI7)
6: JOG commandBy KPC-CC01 or external control
0
02-08
Multi-function Input Command 8
(MI8)
7: Acceleration/deceleration speed inhibit 0
02-26
Input terminal of I/O
extension card (MI10)
8: The 1
st
, 2
nd
acceleration/deceleration time selection 0
02-27
Input terminal of I/O extension
card (MI11)
9: The 3
rd
, 4
th
acceleration/deceleration time selection 0
02-28
Input terminal of I/O extension
card (MI12)
10: EF Input (Pr.07-20) 0
02-29
Input terminal of I/O extension
card (MI13)
11: B.B input from external (Base Block) 0
02-30
Input terminal of I/O extension
card (MI14)
12: Output stop 0
02-31 13: Cancel the setting of optimal accel. /decel. time 0
14: Switch between motor 1 and motor 2
15: Operation speed command from AVI
Input terminal of I/O extension
card (MI15)
16: Operation speed command from ACI
17: Operation speed command from AUI
18: Emergency stop (Pr.07-20)
19: Digital up command
20: Digital down command
21: PID function disabled
22: Clear counter
23: Input the counter value (MI6)
24: FWD JOG command
25: REV JOG command
26: TQC/FOCmodel selection
27: ASR1/ASR2 selection
28: Emergency stop (EF1)
29: Signal confirmation for Y-connection
30: Signal confirmation for -connection
31: High torque bias (Pr.11-30)
32: Middle torque bias (Pr.11-31)
33: Low torque bias (Pr.11-32)
34: Switch between multi-step position and
multi-speed control
35: Enable single point position control
36: Enable multi-step position learning function (valid
at stop)
37: Full position control pulse command input enable