Delta Electronics VFD037CH23A-21 [56/638] Main circuit terminals r l1 s l2 t l3 u t1 v t2 w t3 b1 b2 1 2

Превью страниц Страница 56 / 638
Delta Electronics VFD450CH23A-00/-21 [56/638] Main circuit terminals r l1 s l2 t l3 u t1 v t2 w t3 b1 b2 1 2
Chapter 5 Main Circuit Terminals
5-5
5-1 Main Circuit Terminals
Frame A
Main circuit terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , B1, B2, +1, +2, -
Models
Max. Wire
Gauge
Min. Wire Gauge
Torque
(±10%)
VFD007CH23A-21 14 AWG (2.1mm
2
)
VFD015CH23A-21 12 AWG (3.3mm
2
)
VFD022CH23A-21 10 AWG (5.3mm
2
)
VFD037CH23A-21 8 AWG (8.4mm
2
)
VFD007CH43A-21 14 AWG (2.1mm
2
)
VFD007CH4EA-21 14 AWG (2.1mm
2
)
VFD015CH43A-21 14 AWG (2.1mm
2
)
VFD015CH4EA-21 14 AWG (2.1mm
2
)
VFD022CH43A-21 14 AWG (2.1mm
2
)
VFD022CH4EA-21 14 AWG (2.1mm
2
)
VFD037CH43A-21 10 AWG (5.3mm
2
)
VFD037CH4EA-21 10 AWG (5.3mm
2
)
VFD055CH43A-21 10 AWG (5.3mm
2
)
VFD055CH4EA-21
8 AWG
(8.4mm
2
)
10 AWG (5.3mm
2
)
M4
20kg-cm
(17.4 lb-in.)
(1.962Nm)
UL installations must use 600V, 75 or 90 wire. Use copper wire
only.
1. Figure 1 shows the terminal specification.
2. Figure 2 shows the specification of insulated heat shrink tubing that
comply with UL (600V, YDPU2).
Figure 1
Figure 2