Delta Electronics VFD037CH23A-21 — настройки параметров для управления температурой двигателя [340/638]

Превью страниц Страница 340 / 638
Delta Electronics VFD037CH23A-21 [340/638] Removable terminal block
Chapter 12 Description of Parameter SettingsCH2000 Series
124
12-
MI1+24V
COM
FWD
MO1
MI5
MI3
ACI+10V
AVI
AFM1
MO2 MCM MI7
MI4DCM REV MI2S1 MI8MI6ACM-10V AUI
AFM2
SCM DFM SG-SG+
RA2RC2 RB2 RB1RC1 RA1
0-10V
-10-10V
0-10V
0-10V
0-10V
0-20mA
0-20mA
0-20mA Open
120
AFM1
AFM2
AVI
ACI
485
Removable Terminal Block
PT100
SGND
Figure 1
When Pr.06-58=0.00Hz, PT100 function is disabled.
Example:
A PT100 is installed to the drive. If motor temperature reaches 135 (275°F) or higher, the drive
will decrease motor frequency to the setting of Pr.06-58. Motor will operate at this frequency
(Pr.06-58) till the motor temperature decreases to 135(275°F) or lower. If motor temperature
exceeds 150(302°F), the motor will decelerate to stop and outputs an ‘OH3’ warning.
Set up process:
1. Switch AFM2 (SW2) to 0-20mA on the I/O control terminal block. (Refer to Figure 1, PT100 wiring
diagram)
2. Wiring (Refer to Figure 1, PT100 wiring diagram):
Connect external terminal AFM2 to (+)
Connect external terminal ACM to (-)
Connect external terminals AFM2 and AVI to short-circuit
3. Set Pr.03-00=11 or Pr.03-23=23 or Pr.03-33=45%(9mA)
4. Refer to RTD temperature and resistance comparison table
Temperature=135 , resistance=151.71; Input current: 9mA, Voltage: approximately: 1.37Vdc
Temperature=150 , resistance=157.33; Input current:9mA, Voltage: approximately: 1.42Vdc
5. Set Pr.06=56=1.37 and Pr.06-58=10Hz. When RTD temperature increases to 135 or higher,
the drive will decelerate to the selected frequency. When Pr.06-58=0, the drive will not run.
6. Set Pr.06-57=1.42 and Pr.06-29=1 (warning and decelerate to stop). When RTD temperature
increases to 150 or higher, the drive will decelerate to stop and outputs an OH3 warning.
Reserved
Software Detection GFF Current Level
Factory Setting: 60.0
Settings 0.0~6553.5 %
Software Detection GFF Filter Time
Factory Setting: 0.10
Settings 0.0~6553.5 %
When the motor drive detects the unbalanced three-phase out current is higher than the setting of
Pr06-60, GFF protection will be activated. Then the motor drive will stop outputting.