Chapter 12 Description of Parameter SettingsCH2000 Series
125
12-
When 3-phase current output unbalance value has exceeds Pr06-60 setting, drive will trip up GFF
and stop output immediately.
Disable Level of dEb
Factory Setting: 180.0/360.0
Settings 230V series: 0.0~220.0 Vic
460V series: 0.0~440.0 Vic
Fault Record 1 (day)
Fault Record 2 (day)
Fault Record 3 (day)
Fault Record 4 (day)
Factory Setting: Read only
Settings 0~65535 days
Fault Record 1 (min)
Fault Record 2 (min)
Fault Record 3 (min)
Fault Record 4 (min)
Factory Setting: Read only
Settings 0~1439 min
Pr.06-63 to Pr.06-68 are used to record the operation time for 6 malfunctions and it can also check
if there is any wrong with the drive according to the internal time.
When the malfunction occurs during operation, it records fault in Pr.06-17~06-22 and operation
time is recorded in Pr.06-63~06-68.
For example: When the first fault ovA occurs after operation 3000 min., second fault ovd occurs at
3482 min., third fault ovA occurs at 4051 min., fourth fault ocA at 5003 min., fifth fault ocA at 5824
min., sixth fault ocd occurs at 6402 min. and seven fault ocS at 6951 min..
It’ll be recorded as the following table: