Chapter 14 Fault Codes and Descriptions CH2000 Series
14-8
ID* Fault Name Fault Descriptions Corrective Actions
68
SdRv
SpdFbk Dir Rev
Fault
Rotating direction is different from the commanding direction detected by the
sensorless.
Solution
Verify if the parameter setting of the motor drive is correct
Increase the estimator's bandwidth and verify if parameters relating to the
sensorless are correct.
69
SdOr
SpdFbk over SPD
Fault
Overspeed rotation detected by the sensorless
Solution
Verify if the parameter setting of the motor drive is correct
Increase the estimator's bandwidth and verify if parameters relating to the
sensorless are correct.
Verify if the gains of the speed circuit is reasonable.
70
SdDe
SpdFbk deviate
Fault
Big difference between the rotating speed and the command detected by the
sensorless
Solution
Verify if the parameter setting of the motor drive is correct
Increase the estimator's bandwidth and verify if parameters relating to the
sensorless are correct.
Verify if the gains of the speed circuit is reasonable.
73
S1
S1-emergy stop
Fault
Emergency stop for external safety
79
Uoc
U phase oc
Fault
Phase U short circuit
80
Voc
V phase oc
Fault
Phase V short circuit
81
Woc
W phase oc
Fault
W phase short circuit
82
OPHL
U phase lacked
Fault
Output phase loss (Phase U)
83
OPHL
V phase lacked
Fault
Output phase loss (Phase V)