Chapter 12 Description of Parameter SettingsCH2000 Series
12-1
Chapter 12 Description of Parameter Settings
00 Drive Parameters This parameter can be set during operation.
Identity Code of the AC Motor Drive
Factory Setting: #.#
Settings Read Only
Display AC Motor Drive Rated Current
Factory Setting: #.#
Settings Read Only
Pr. 00-00 displays the identity code of the AC motor drive. Using the following table to check if
Pr.00-01 setting is the rated current of the AC motor drive. Pr.00-01 corresponds to the identity
code Pr.00-00.
230V Series
Frame A B C
kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5
HP 1.0 2.0 3.0 5.0 7.5 10 15 20 25
Pr.00-00 4 6 8 10 12 14 16 18 20
Rated Current for
Super Heavy Duty
(A)
5 8 11 17 25 33 49 65 75
Frame D E F
kW 22 30 37 45 50 75
HP 30 40 50 60 75 100
Pr.00-00 22 24 26 28 30 32
Rated Current for
Super Heavy Duty
(A)
90 120 146 180 215 255
460V Series
Frame
A B C
kW 0.75 1.5 2.2 3.7 5.5 7. 5 11 15 18.5 22 30
HP 1 2 3 5 7.5 10 15 20 25 30 40
Pr.00-00 5 7 9 11 13 15 17 19 21 23 25
Rated Current for
Super Heavy Duty
(A)
3.0 4.0 6.0 9.0 12 18 24 32 38 45 60
Frame D E F G H
kW
37 45 55 75 90 110 132 160 185 220 280
HP
50 60 75 100 125 150 175 215 250 300 375
Pr.00-00
27 29 31 33 35 37 39 41 43 45 47
Rated Current for
Super Heavy Duty
(A)
73 91 110 150 180 220 250 310 370 450 550
Parameter Reset
Factory Setting: 0